Vertex M helps facilities effectively safeguard against downtime by combining the most advanced Chemcassette® optics technologies and built-in system redundancies. Vertex M is a flexible, easy-to-use and reliable gas monitoring system. As your monitoring needs change, Vertex M expands its offering to as little as eight points and up to 24 points of continuous gas detection.
The Vertex system can accept sampling points up to 400 feet (120 meters) from the central unit. Vertex M can also accept a mix of universal analyzer modules and pyrolyzer analyzers. The system monitors a wide variety of gases present in semiconductor fabrication with sensitivity as low as parts per billion (ppb).
Even the best products deserve expert maintenance!

Elevate your gas detectors’ potential with Honeywell's expert maintenance services! Maximize uptime, eliminate costs, and ensure on-time, on-budget project completion.

Explore our fixed, portable, and high-tech support services now!

Specifications

Brand

  • Brand
    • Honeywell

Dimensions & Weight

  • Size
    • H: 56 in D: 36 in W: 24 in
  • Sampling Distance
    • Up to 400ft
  • Exhaust Length
    • 50 ft

Technical Specifications

  • Digital Communication Ports
    • ControlNet
    • DF1
    • DeviceNet
    • Ethernet/CIP
    • LonWorks
    • ModBus Plus
    • Modbus/TCP
    • Profibus - DP
  • Operating Altitude
    • -1,000 ft to 6,000 ft Above Sea Level
  • Network Interface
    • OLE for Process Control (OPC) Interface
  • Analog Outputs
    • 4 to 20 mA (24 Channels)
  • Sample Lines
    • ID: 0.156 in OD: 1/4 in FEP Teflon
    • ID: 0.190 in OD: 1/4 in FEP Teflon
  • Exhaust Line
    • ID: 3/8 in OD: 1/2 in Polypropylene
  • Relays
    • Isolated (08X) or Non-Isolated (016X)
    • PLC: 32 Relays for 8 Channel Isolated Relay Option; 64 Relays Total for 16 Channel Non-Isolated Relay Option

Standards & Certifications

  • Certificates and Standards
    • CE Certified
    • EN 300 330-1 V1.8.1
    • EN 301 489-1 V1.9.2
    • EN 50270:2015
    • EN 61010-1:2010
    • EN IEC 63000:2018
    • EN ISO/IEC 17050-1:2010
    • RoHS

Features

  • Features & Benefits
    • 8 to 24 Point Toxic Gas Monitor Configurable for Use with up to 3 Universal Chemcassette Analyzers or Combination 1 Pyrolyzer Analyzer/1 Universal Chemcassette Analyzer
  • Visual Indicators
    • 1024 x 768 pixel Touch Screen with at-a-Glance System Status
  • Display Type
    • 1024 x 768 pixel Touch Screen with at-a-Glance System Status
  • Alarm Type
    • Capable of A1 and A2 Alarms per Point, per Point Maintenance/Instrument Faults, as well as General Analyzer A1, General Analyzer A2, and General Analyzer Instrument/Maintenance Faults

Operating Characteristics

  • Operating Humidity
    • 20 to 65% RH

Electrical Specifications

  • Power Requirement
    • 110/230 V AC
  • Operating Voltage
    • 110 or 230 V AC ± 10% (Under Load) @50/60 Hz; 15A

Applications & Compatibility

  • For Use With
    • Universal Chemcassette Analyzers and Pyrolyzer Analyzer

Brand

  • Brand
    • Honeywell

Dimensions & Weight

  • Size
    • H: 56 in D: 36 in W: 24 in
  • Sampling Distance
    • Up to 400ft
  • Exhaust Length
    • 50 ft

Technical Specifications

  • Digital Communication Ports
    • ControlNet
    • DF1
    • DeviceNet
    • Ethernet/CIP
    • LonWorks
    • ModBus Plus
    • Modbus/TCP
    • Profibus - DP
  • Operating Altitude
    • -1,000 ft to 6,000 ft Above Sea Level
  • Network Interface
    • OLE for Process Control (OPC) Interface
  • Analog Outputs
    • 4 to 20 mA (24 Channels)
  • Sample Lines
    • ID: 0.156 in OD: 1/4 in FEP Teflon
    • ID: 0.190 in OD: 1/4 in FEP Teflon
  • Exhaust Line
    • ID: 3/8 in OD: 1/2 in Polypropylene
  • Relays
    • Isolated (08X) or Non-Isolated (016X)
    • PLC: 32 Relays for 8 Channel Isolated Relay Option; 64 Relays Total for 16 Channel Non-Isolated Relay Option

Standards & Certifications

  • Certificates and Standards
    • CE Certified
    • EN 300 330-1 V1.8.1
    • EN 301 489-1 V1.9.2
    • EN 50270:2015
    • EN 61010-1:2010
    • EN IEC 63000:2018
    • EN ISO/IEC 17050-1:2010
    • RoHS

Features

  • Features & Benefits
    • 8 to 24 Point Toxic Gas Monitor Configurable for Use with up to 3 Universal Chemcassette Analyzers or Combination 1 Pyrolyzer Analyzer/1 Universal Chemcassette Analyzer
  • Visual Indicators
    • 1024 x 768 pixel Touch Screen with at-a-Glance System Status
  • Display Type
    • 1024 x 768 pixel Touch Screen with at-a-Glance System Status
  • Alarm Type
    • Capable of A1 and A2 Alarms per Point, per Point Maintenance/Instrument Faults, as well as General Analyzer A1, General Analyzer A2, and General Analyzer Instrument/Maintenance Faults

Operating Characteristics

  • Operating Humidity
    • 20 to 65% RH

Electrical Specifications

  • Power Requirement
    • 110/230 V AC
  • Operating Voltage
    • 110 or 230 V AC ± 10% (Under Load) @50/60 Hz; 15A

Applications & Compatibility

  • For Use With
    • Universal Chemcassette Analyzers and Pyrolyzer Analyzer
  • Brand : Honeywell
  • Size : H: 56 in D: 36 in W: 24 in
  • Digital Communication Ports : ControlNet|DF1|DeviceNet|Ethernet/CIP|LonWorks|ModBus Plus|Modbus/TCP|Profibus - DP
  • Certificates and Standards : CE Certified|EN 300 330-1 V1.8.1|EN 301 489-1 V1.9.2|EN 50270:2015|EN 61010-1:2010|EN IEC 63000:2018|EN ISO/IEC 17050-1:2010|RoHS
  • Features & Benefits : 8 to 24 Point Toxic Gas Monitor Configurable for Use with up to 3 Universal Chemcassette Analyzers or Combination 1 Pyrolyzer Analyzer/1 Universal Chemcassette Analyzer
  • Operating Humidity : 20 to 65% RH
  • Operating Altitude : -1,000 ft to 6,000 ft Above Sea Level
  • Visual Indicators : 1024 x 768 pixel Touch Screen with at-a-Glance System Status
  • Sampling Distance : Up to 400ft
  • Power Requirement : 110/230 V AC
  • Operating Voltage : 110 or 230 V AC ± 10% (Under Load) @50/60 Hz; 15A
  • Network Interface : OLE for Process Control (OPC) Interface
  • Exhaust Length : 50 ft
  • Analog Outputs : 4 to 20 mA (24 Channels)
  • Sample Lines : ID: 0.156 in OD: 1/4 in FEP Teflon|ID: 0.190 in OD: 1/4 in FEP Teflon
  • For Use With : Universal Chemcassette Analyzers and Pyrolyzer Analyzer
  • Exhaust Line : ID: 3/8 in OD: 1/2 in Polypropylene
  • Display Type : 1024 x 768 pixel Touch Screen with at-a-Glance System Status
  • Alarm Type : Capable of A1 and A2 Alarms per Point, per Point Maintenance/Instrument Faults, as well as General Analyzer A1, General Analyzer A2, and General Analyzer Instrument/Maintenance Faults
  • Relays : Isolated (08X) or Non-Isolated (016X)|PLC: 32 Relays for 8 Channel Isolated Relay Option; 64 Relays Total for 16 Channel Non-Isolated Relay Option
Manuals and Guides
Name
Description
File Size
Date
Size
Vertex M User Manual
application/pdf 69.19 MB
7/1/2024
69.19 MB
Vertex M Multi-Point Toxic Gas Monitoring System - User Manual - English
application/pdf 10.96 MB
5/17/2022
10.96 MB
Technical Note
Name
Description
File Size
Date
Size
TN MVIP3504-TN Vertex M Profibus
application/pdf 91.02 KB
12/20/2021
91.02 KB
TN Vertex M - Vertex Window Pattern
application/pdf 143.01 KB
12/20/2021
143.01 KB
TN 1998-0546 Vertex M Hydrogen Sulfide Scrubber filter
application/pdf 58.72 KB
8/1/2023
58.72 KB
TN 1998-0568 Vertex M Vertex Config external PC
application/pdf 279.91 KB
12/20/2021
279.91 KB
TN 1295-0566 Vertex Line Integrity Test Option
application/pdf 181.36 KB
12/20/2021
181.36 KB
Vertex M Specification Sheet
application/pdf 213.7 KB
12/20/2021
213.7 KB
TN 1998-0736 Vertex M V1.23 Tech Note
application/pdf 132.03 KB
12/20/2021
132.03 KB
TN 1998M0765 Vertex M R1 Vertex M Unpacking Instructions
application/pdf 959.42 KB
12/20/2021
959.42 KB
TN 1998-0632 Vertex M Vertex touch screen
application/pdf 72.29 KB
12/20/2021
72.29 KB
TN 1998-0635 Vertex M AZ Manual Override TN
application/pdf 493.03 KB
12/20/2021
493.03 KB
TN 1998-0477 Vertex M - Vertex ChemCam Setup
application/pdf 145.87 KB
12/20/2021
145.87 KB
TN 1998-0496 Vertex M - Vertex Active Display Setup
application/pdf 124.66 KB
12/20/2021
124.66 KB
Vertex & Vertex M - Product Notice
application/pdf 119.37 KB
10/21/2022
119.37 KB
TN 1998 1025 Vertex and Vertex M DAq Computer OS Compatibility
application/pdf 159.34 KB
12/20/2021
159.34 KB
TN 1998-0407 Vertex Remote View/Control Option
application/pdf 47.87 KB
12/20/2021
47.87 KB
Certificate
Name
Description
File Size
Date
Size
Vertex M and Vertex EU Declaration of Conformity
application/pdf 172.02 KB
1/5/2022
172.02 KB
Vertex and Vertex M - EU Declaration of Conformity
application/pdf 189.3 KB
2/2/2023
189.3 KB
Name
Description
File Size
Date
Size
TN MVIP3504-TN Vertex M Profibus
application/pdf 91.02 KB
12/20/2021
91.02 KB
TN Vertex M - Vertex Window Pattern
application/pdf 143.01 KB
12/20/2021
143.01 KB
TN 1998-0546 Vertex M Hydrogen Sulfide Scrubber filter
application/pdf 58.72 KB
8/1/2023
58.72 KB
Vertex M User Manual
application/pdf 69.19 MB
7/1/2024
69.19 MB
TN 1998-0568 Vertex M Vertex Config external PC
application/pdf 279.91 KB
12/20/2021
279.91 KB
TN 1295-0566 Vertex Line Integrity Test Option
application/pdf 181.36 KB
12/20/2021
181.36 KB
Vertex M Specification Sheet
application/pdf 213.7 KB
12/20/2021
213.7 KB
Vertex M Multi-Point Toxic Gas Monitoring System - User Manual - English
application/pdf 10.96 MB
5/17/2022
10.96 MB
Vertex M and Vertex EU Declaration of Conformity
application/pdf 172.02 KB
1/5/2022
172.02 KB
TN 1998-0736 Vertex M V1.23 Tech Note
application/pdf 132.03 KB
12/20/2021
132.03 KB
TN 1998M0765 Vertex M R1 Vertex M Unpacking Instructions
application/pdf 959.42 KB
12/20/2021
959.42 KB
TN 1998-0632 Vertex M Vertex touch screen
application/pdf 72.29 KB
12/20/2021
72.29 KB
Vertex and Vertex M - EU Declaration of Conformity
application/pdf 189.3 KB
2/2/2023
189.3 KB
TN 1998-0635 Vertex M AZ Manual Override TN
application/pdf 493.03 KB
12/20/2021
493.03 KB
TN 1998-0477 Vertex M - Vertex ChemCam Setup
application/pdf 145.87 KB
12/20/2021
145.87 KB
TN 1998-0496 Vertex M - Vertex Active Display Setup
application/pdf 124.66 KB
12/20/2021
124.66 KB
Vertex & Vertex M - Product Notice
application/pdf 119.37 KB
10/21/2022
119.37 KB
TN 1998 1025 Vertex and Vertex M DAq Computer OS Compatibility
application/pdf 159.34 KB
12/20/2021
159.34 KB
TN 1998-0407 Vertex Remote View/Control Option
application/pdf 47.87 KB
12/20/2021
47.87 KB
Showing 1 to 10 of 17 parts
Product Number
Part Number
Description
Leaf Category
Thumbnail
1283K1090
Sample Line Tubing Duct Adapter: Midas Gas Detector Accessories
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1283K1090
Sample Line Tubing Duct Adapter: Midas Gas Detector Accessories
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0066
110 VAC Vertex M Base Rack
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0066
110 VAC Vertex M Base Rack
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0071
220 VAC Vertex M Base Rack
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0071
220 VAC Vertex M Base Rack
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0072
Vertex M™ with one (1) Universal Chemcassette Analyzer: This configuration contains a Vertex M™ Base Rack (110 VAC) with one (1) universal chemcassette analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0072
Vertex M™ with one (1) Universal Chemcassette Analyzer: This configuration contains a Vertex M™ Base Rack (110 VAC) with one (1) universal chemcassette analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0073
Vertex M™ with one (1) Pyrolyzer Analyzer: This configuration contains a Vertex M™ Base Rack (110 VAC) with one (1) pyrolyzer analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0073
Vertex M™ with one (1) Pyrolyzer Analyzer: This configuration contains a Vertex M™ Base Rack (110 VAC) with one (1) pyrolyzer analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0074
Vertex M™ with one (1) Universal Chemcassette Analyzer: This configuration contains a Vertex M™ Base Rack (220 VAC) with one (1) universal chemcassette analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0074
Vertex M™ with one (1) Universal Chemcassette Analyzer: This configuration contains a Vertex M™ Base Rack (220 VAC) with one (1) universal chemcassette analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0075
Vertex M™ with one (1) Pyrolyzer Analyzer: This configuration contains a Vertex M™ Base Rack (220 VAC) with one (1) pyrolyzer analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0075
Vertex M™ with one (1) Pyrolyzer Analyzer: This configuration contains a Vertex M™ Base Rack (220 VAC) with one (1) pyrolyzer analyzer, the data acquisition center, redundant pumps and power supplies, touch screen keyboard.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0076
16 Channel Non-Isolated Relay OptionTotal of sixty-four (64) factory installed and field programmable Form A relays. Within each group of eight relays one side connected to a common terminal.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0076
16 Channel Non-Isolated Relay OptionTotal of sixty-four (64) factory installed and field programmable Form A relays. Within each group of eight relays one side connected to a common terminal.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0077
8 Channel Isolated Relay OptionTotal of thirty-two (32) factory installed and field programmable Form A relays. Each contact totally isolated.
https://honeywell.scene7.com/is/image/Honeywell65/sps-analytics-vertex-m-image-3
1290-0077
8 Channel Isolated Relay OptionTotal of thirty-two (32) factory installed and field programmable Form A relays. Each contact totally isolated.