/content/sps/au/en/search-results.html

    fixed gas detectors

    SS4 Flame Detector

    Electro-Optical Digital Fire and Flame Detectors

    Overview

    Electro-optical digital detectors represent leading edge UV and UV/IR technology.

    Product Overview:

    SS4-A:

    The SS4-A represents the world’s pre-eminent UV/IR technology for Electro-Optical Flame Detectors with tens of thousands successfully operating in a multitude of installations worldwide. This multi-spectrum detector senses radiant energy in the ultraviolet (UV), visible and Wide Band Infrared™ (IR) spectrum. The radiant energy from all types of flaming fires will alert the detector to their presence.

    To eliminate common nuisance false alarms that occasionally occur with UV-only, IR-only, Dual IR or Dual Mode UV/IR detectors, the SS4 Flame Detectors’ FireLogic signal processing requires that UV, visible and Wide Band IR radiant energy all be evaluated before declaring a fire. The smart detector utilizes real-time signal processing algorithms that are optimized to alarm on all types of fires, while virtually eliminating the possibility of false alarms.

    SS4-AS:

    The SS4-AS processes UV, IR and Visible (VIS) spectral ranges from ruggedized solar-blind UV, “Quantum-Effect” IR and VIS sensors correspondingly. It is optimized for detection of hydrogen, ethanol, methanol and methane (natural gas) fires and like the other detectors in its family, it responds to Type A, B and C flaming fires.

    SS4-AUV:

    The SS4-AUV represents the leading edge technology UV optical flame detectors. This flame detector senses radiant energy in the ultraviolet (UV) spectrum. The radiant emissions of flaming fires will alert the detector to their presence.

    Additional Features and Benefits:

    SS4-A and SS4-AS Features:

    • Multi-Spectrum™: senses ultraviolet, visible and Wide Band Infrared™
    • Built-in test for optical “through the lens” testing
    • False alarm immunity
    • Detects hydrocarbon and non-hydrocarbon based fires
    • Wide field-of-view and solar-blind
    • Adjustable detector sensitivity
    • Microprocessor based algorithms: FirePic™, Snapshot™ and Tri-Mode Plot™
    • Wide temperature range of operation
    • Compatible with standard approved fire alarm panels
    • Explosion-proof housing
    • Time programmable alarm verification

    SS4-AUV Features:

    • Senses solar-blink ultraviolet band
    • Built-in test for optical “through the lens” testing
    • Utilizes long-life, ruggedized UV sensors
    • Detects hydrocarbon and non-hydrocarbon based fires
    • Wide field-of-view and solar-blind
    • Adjustable detector sensitivity
    • Microcomputer based algorithms: FirePic™, Snapshot™ and UV Plot
    • Wide temperature range of operation
    • Compatible with standard approved fire alarm panels
    • Explosion-proof housing
    • Time programmable alarm verification.

    Features & Benefits:

    • Detects hydrocarbon and non-hydrocarbon based fires
    • Built-in test for optical “through the lens” testing
    • False alarm immunity

    Quick Specs:

    • Sensitivity: Adjustable between 60 ft., 45 ft., 30 ft., and 15 ft. to a 1 sq. ft. gasoline fire
    • Response time: 2-5 seconds to 1 sq. ft. of gasoline fire at 60 ft.
    • Field-of-view: 120 degrees cone of vision (60 degrees from on axis)

    Fire and Gas Consultancy Services

    Even the best products deserve expert maintenance!

    Elevate your gas detectors’ potential with Honeywell's expert maintenance services! Maximize uptime, eliminate costs, and ensure on-time, on-budget project completion.

    Explore our fixed, portable, and high-tech support services now!

    Specifications

    Overview

    • Brand
      • Honeywell
      • Honeywell
    • Warranty
      • 2 Years from Date of Shipping

    Features

    • Sub-Category
      • Flame Detectors
    • Features & Benefits
      • Adjustable Detector Sensitivity
      • Adjustable Detector Sensitivity
      • Available SS4-A, SS4-AS and SS4-AUV
      • Built-In Test For Optical “Through The Lens” Testing
      • Built-In Test For Optical “Through The Lens” Testing
      • Compatible with Standard Approved Fire Alarm Panels
      • Compatible with Standard Approved Fire Alarm Panels
      • Detects Hydrocarbon and Non-Hydrocarbon Fires
      • Detects Hydrocarbon and Non-Hydrocarbon Fires
      • Explosion-Proof Housing
      • Explosion-Proof Housing
      • False Alarm Immunity
      • Microcomputer Based Algorithms: FirePic™, Snapshot™ and UV Plot
      • Microprocessor Based Algorithms: FirePic™, Snapshot™ and Tri-Mode Plot™
      • Multi-Spectrum Senses Energy in the UV, Vis and WideBand IR™
      • Senses Solar-Blink Ultraviolet Band
      • Time Programmable Alarm Verification
      • Time Programmable Alarm Verification
      • Utilizes Long-Life, Ruggedized UV Sensors
      • Wide Field of View and Solar Blind
      • Wide Field of View and Solar Blind
      • Wide Temperature Range of Operation
      • Wide Temperature Range of Operation

    Dimensions & Weight

    • Weight range
      • Aluminum: 4 lbs
      • Stainless Steel: 7.5 lbs

    Technical Specifications

    • Humidity Range
      • 5 to 98% RH (Non-Condensing)
    • Relay Output Configuration
      • Fault Relay: NO & NC Contacts
      • Fire Alarm Relay: NO & NC Contacts, Latching/Non-Latching, Switch Selectable
      • Fire Verify Relay: NO & NC Contacts, Adjustable Time From 0 to 30 sec
      • Relay Contact Ratings: 0.5A @120 VAC, 1.0A @24 VDC
    • Mounting
      • Swivel Bracket Assembly
    • Spectral Sensitivity
      • Ultraviolet: 185 to 260 Nanometers
      • Visible: 400 to 700 Nanometers
      • Wide Band Infrared: 0.7 to 3.5 micrometers
    • Conduit Entries
      • 3/4 in NPT
    • Field of View
      • From Cone of Vision: 120 deg
      • From On Axis: 60 deg

    Operating Characteristics

    • Minimum Temperature
      • -40˚C

    Standards & Certifications

    • Ingress Protection
      • IP66
    • NEMA Rating
      • NEMA 4

    Material Specifications

    • Enclosure Material
      • Copper-Free Powder Coated Aluminum

    Electrical Specifications

    • Power Requirement
      • 24 VDC
    • Power Consumption
      • 68 mA Normal Operation (Relay Version)
      • 75 mA Alarm Condition (Relay Version)
      • 95 mA Alarm Condition (Analog Version)

    Applications & Compatibility

    • Application
      • Aircraft Hangars
      • Co-Generation Plants
      • Gas Compressor Stations
      • Gas Turbines & Power Plants
      • Silane and Hydrogen Gas Storage
      • Warehouses

    Overview

    • Brand
      • Honeywell
      • Honeywell
    • Warranty
      • 2 Years from Date of Shipping

    Features

    • Sub-Category
      • Flame Detectors
    • Features & Benefits
      • Adjustable Detector Sensitivity
      • Adjustable Detector Sensitivity
      • Available SS4-A, SS4-AS and SS4-AUV
      • Built-In Test For Optical “Through The Lens” Testing
      • Built-In Test For Optical “Through The Lens” Testing
      • Compatible with Standard Approved Fire Alarm Panels
      • Compatible with Standard Approved Fire Alarm Panels
      • Detects Hydrocarbon and Non-Hydrocarbon Fires
      • Detects Hydrocarbon and Non-Hydrocarbon Fires
      • Explosion-Proof Housing
      • Explosion-Proof Housing
      • False Alarm Immunity
      • Microcomputer Based Algorithms: FirePic™, Snapshot™ and UV Plot
      • Microprocessor Based Algorithms: FirePic™, Snapshot™ and Tri-Mode Plot™
      • Multi-Spectrum Senses Energy in the UV, Vis and WideBand IR™
      • Senses Solar-Blink Ultraviolet Band
      • Time Programmable Alarm Verification
      • Time Programmable Alarm Verification
      • Utilizes Long-Life, Ruggedized UV Sensors
      • Wide Field of View and Solar Blind
      • Wide Field of View and Solar Blind
      • Wide Temperature Range of Operation
      • Wide Temperature Range of Operation

    Dimensions & Weight

    • Weight range
      • Aluminum: 4 lbs
      • Stainless Steel: 7.5 lbs

    Technical Specifications

    • Humidity Range
      • 5 to 98% RH (Non-Condensing)
    • Relay Output Configuration
      • Fault Relay: NO & NC Contacts
      • Fire Alarm Relay: NO & NC Contacts, Latching/Non-Latching, Switch Selectable
      • Fire Verify Relay: NO & NC Contacts, Adjustable Time From 0 to 30 sec
      • Relay Contact Ratings: 0.5A @120 VAC, 1.0A @24 VDC
    • Mounting
      • Swivel Bracket Assembly
    • Spectral Sensitivity
      • Ultraviolet: 185 to 260 Nanometers
      • Visible: 400 to 700 Nanometers
      • Wide Band Infrared: 0.7 to 3.5 micrometers
    • Conduit Entries
      • 3/4 in NPT
    • Field of View
      • From Cone of Vision: 120 deg
      • From On Axis: 60 deg

    Operating Characteristics

    • Minimum Temperature
      • -40˚C

    Standards & Certifications

    • Ingress Protection
      • IP66
    • NEMA Rating
      • NEMA 4

    Material Specifications

    • Enclosure Material
      • Copper-Free Powder Coated Aluminum

    Electrical Specifications

    • Power Requirement
      • 24 VDC
    • Power Consumption
      • 68 mA Normal Operation (Relay Version)
      • 75 mA Alarm Condition (Relay Version)
      • 95 mA Alarm Condition (Analog Version)

    Applications & Compatibility

    • Application
      • Aircraft Hangars
      • Co-Generation Plants
      • Gas Compressor Stations
      • Gas Turbines & Power Plants
      • Silane and Hydrogen Gas Storage
      • Warehouses
    • Brand : Honeywell|Honeywell
    • Sub-Category : Flame Detectors
    • Weight range : Aluminum: 4 lbs|Stainless Steel: 7.5 lbs
    • Humidity Range : 5 to 98% RH (Non-Condensing)
    • Minimum Temperature : -40˚C
    • Features & Benefits : Adjustable Detector Sensitivity|Adjustable Detector Sensitivity|Available SS4-A, SS4-AS and SS4-AUV|Built-In Test For Optical “Through The Lens” Testing|Built-In Test For Optical “Through The Lens” Testing|Compatible with Standard Approved Fire Alarm Panels|Compatible with Standard Approved Fire Alarm Panels|Detects Hydrocarbon and Non-Hydrocarbon Fires|Detects Hydrocarbon and Non-Hydrocarbon Fires|Explosion-Proof Housing|Explosion-Proof Housing|False Alarm Immunity|Microcomputer Based Algorithms: FirePic™, Snapshot™ and UV Plot|Microprocessor Based Algorithms: FirePic™, Snapshot™ and Tri-Mode Plot™|Multi-Spectrum Senses Energy in the UV, Vis and WideBand IR™|Senses Solar-Blink Ultraviolet Band|Time Programmable Alarm Verification|Time Programmable Alarm Verification|Utilizes Long-Life, Ruggedized UV Sensors|Wide Field of View and Solar Blind|Wide Field of View and Solar Blind|Wide Temperature Range of Operation|Wide Temperature Range of Operation
    • Relay Output Configuration : Fault Relay: NO & NC Contacts|Fire Alarm Relay: NO & NC Contacts, Latching/Non-Latching, Switch Selectable|Fire Verify Relay: NO & NC Contacts, Adjustable Time From 0 to 30 sec|Relay Contact Ratings: 0.5A @120 VAC, 1.0A @24 VDC
    • Ingress Protection : IP66
    • NEMA Rating : NEMA 4
    • Mounting : Swivel Bracket Assembly
    • Spectral Sensitivity : Ultraviolet: 185 to 260 Nanometers|Visible: 400 to 700 Nanometers|Wide Band Infrared: 0.7 to 3.5 micrometers
    • Enclosure Material : Copper-Free Powder Coated Aluminum
    • Power Requirement : 24 VDC
    • Power Consumption : 68 mA Normal Operation (Relay Version)|75 mA Alarm Condition (Relay Version)|95 mA Alarm Condition (Analog Version)
    • Conduit Entries : 3/4 in NPT
    • Field of View : From Cone of Vision: 120 deg|From On Axis: 60 deg
    • Application : Aircraft Hangars|Co-Generation Plants|Gas Compressor Stations|Gas Turbines & Power Plants|Silane and Hydrogen Gas Storage|Warehouses
    • Warranty : 2 Years from Date of Shipping
    Manuals and Guides
    Name
    Description
    File Size
    Date
    Size
    SS4 Flame Detector User Guide
    application/pdf 164.71 KB
    7/15/2021
    164.71 KB
    FSL100 Flame Detectors,FS10-R,FS24X Flame Detector,SS2 Flame Detector,FS20X Flame Detector,SS4 Flame Detector - Product Guide
    application/pdf 2.59 MB
    5/28/2026
    2.59 MB
    SS4 Flame Detector - SS4-A/-A2 - User Manual
    application/pdf 437.92 KB
    4/11/2023
    437.92 KB
    Brochure
    Name
    Description
    File Size
    Date
    Size
    SS4 Flame Detector - Spec Sheet
    application/pdf 229.67 KB
    4/25/2023
    229.67 KB
    SS4 Flame Detector Brochure
    application/pdf 402.18 KB
    7/15/2021
    402.18 KB
    Certificate
    Name
    Description
    File Size
    Date
    Size
    SS4 Flame Detector Atex Declaration of Conformity
    application/pdf 206.34 KB
    7/15/2021
    206.34 KB
    Inmetro DNV GL - Business Assurance Certificate
    application/pdf 512.68 KB
    10/7/2022
    512.68 KB
    FSX SS4 Certificate of Conformity
    application/pdf 474.98 KB
    7/15/2021
    474.98 KB
    SS4 Flame Detector FM Approval Guide
    application/pdf 109.31 KB
    7/15/2021
    109.31 KB
    FS24X Flame Detector,FS20X Flame Detector,SS2 Flame Detector,SS4 Flame Detector Atex Certificate
    application/pdf 170 KB
    7/15/2021
    170 KB
    FT-2145 Test Lamp ATEX CE EU Declaration of Conformity
    application/pdf 206.94 KB
    7/15/2021
    206.94 KB
    FS24X Flame Detector,FS20X Flame Detector,SS2 Flame Detector,SS4 Flame Detector IECEx Certificate of Conformity
    application/pdf 949.8 KB
    7/15/2021
    949.8 KB
    Name
    Description
    File Size
    Date
    Size
    SS4 Flame Detector User Guide
    application/pdf 164.71 KB
    7/15/2021
    164.71 KB
    SS4 Flame Detector Atex Declaration of Conformity
    application/pdf 206.34 KB
    7/15/2021
    206.34 KB
    SS4 Flame Detector - Spec Sheet
    application/pdf 229.67 KB
    4/25/2023
    229.67 KB
    Inmetro DNV GL - Business Assurance Certificate
    application/pdf 512.68 KB
    10/7/2022
    512.68 KB
    FSX SS4 Certificate of Conformity
    application/pdf 474.98 KB
    7/15/2021
    474.98 KB
    SS4 Flame Detector FM Approval Guide
    application/pdf 109.31 KB
    7/15/2021
    109.31 KB
    FS24X Flame Detector,FS20X Flame Detector,SS2 Flame Detector,SS4 Flame Detector Atex Certificate
    application/pdf 170 KB
    7/15/2021
    170 KB
    FSL100 Flame Detectors,FS10-R,FS24X Flame Detector,SS2 Flame Detector,FS20X Flame Detector,SS4 Flame Detector - Product Guide
    application/pdf 2.59 MB
    5/28/2026
    2.59 MB
    SS4 Flame Detector Brochure
    application/pdf 402.18 KB
    7/15/2021
    402.18 KB
    FT-2145 Test Lamp ATEX CE EU Declaration of Conformity
    application/pdf 206.94 KB
    7/15/2021
    206.94 KB
    SS4 Flame Detector - SS4-A/-A2 - User Manual
    application/pdf 437.92 KB
    4/11/2023
    437.92 KB
    FS24X Flame Detector,FS20X Flame Detector,SS2 Flame Detector,SS4 Flame Detector IECEx Certificate of Conformity
    application/pdf 949.8 KB
    7/15/2021
    949.8 KB
    Name
    Description
    File Size
    Date
    Size
    SS4 Flame Detector User Guide
    164.71 KB
    7/15/2021
    FSL100 Flame Detectors,FS10-R,FS24X Flame Detector,SS2 Flame Detector,FS20X Flame Detector,SS4 Flame Detector - Product Guide
    2.59 MB
    5/28/2026
    SS4 Flame Detector - SS4-A/-A2 - User Manual
    437.92 KB
    4/11/2023
    SS4 Flame Detector - Spec Sheet
    229.67 KB
    4/25/2023
    SS4 Flame Detector Brochure
    402.18 KB
    7/15/2021
    SS4 Flame Detector Atex Declaration of Conformity
    206.34 KB
    7/15/2021
    Inmetro DNV GL - Business Assurance Certificate
    512.68 KB
    10/7/2022
    FSX SS4 Certificate of Conformity
    474.98 KB
    7/15/2021
    SS4 Flame Detector FM Approval Guide
    109.31 KB
    7/15/2021
    FS24X Flame Detector,FS20X Flame Detector,SS2 Flame Detector,SS4 Flame Detector Atex Certificate
    170 KB
    7/15/2021
    FT-2145 Test Lamp ATEX CE EU Declaration of Conformity
    206.94 KB
    7/15/2021
    FS24X Flame Detector,FS20X Flame Detector,SS2 Flame Detector,SS4 Flame Detector IECEx Certificate of Conformity
    949.8 KB
    7/15/2021

    Filters

    Product Number
    Part Number
    Compare
    Description
    Leaf Category
    Thumbnail
    Add to list
    2029-INTERFACE-KIT
    Interface Kit for SS4 Detector, with Universal charger
    2029-INTERFACE-KIT
    Interface Kit for SS4 Detector, with Universal charger
    DASA1-P
    AIR SHIELD
    https://s7d1.scene7.com/is/image/Honeywell65/hbt-fire-dasa1-p-air-shield-primaryimage
    DASA1-P
    AIR SHIELD
    https://s7d1.scene7.com/is/image/Honeywell65/hbt-fire-dasa1-p-air-shield-primaryimage
    DT-3124-0001A
    UV CHECKER LAMP
    DT-3124-0001A
    UV CHECKER LAMP
    FS24X-911-10-6
    Replacement Electronics Module for FS24X Detectors. Module only
    https://honeywell.scene7.com/is/image/Honeywell65/hbt-Fire-P1923636-primaryimage
    FS24X-911-10-6
    Replacement Electronics Module for FS24X Detectors. Module only
    https://honeywell.scene7.com/is/image/Honeywell65/hbt-Fire-P1923636-primaryimage
    SS4-A2-C-E-M
    ALUM UVIR NONLATCH 4-20MA ZONE 1, 2 M25
    SS4-A2-C-E-M
    ALUM UVIR NONLATCH 4-20MA ZONE 1, 2 M25
    SS4-A2-CSS-E
    SS UVIR Fire Detector ATEX M25
    SS4-A2-CSS-E
    SS UVIR Fire Detector ATEX M25
    SS4-A2-CSS-E-H
    SS4-A2-CSS-E Stainless Steel UVIR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, ATEX, IECEx FOR Zone 1 (2) M25 with SS4-FSCHCOM SS4 Module HART Factory installed.
    SS4-A2-CSS-E-H
    SS4-A2-CSS-E Stainless Steel UVIR, ATEX, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, ATEX, IECEx FOR Zone 1 (2) M25 with SS4-FSCHCOM SS4 Module HART Factory installed.
    SS4-A2-H
    SS4-A2 Aluminum UVIR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, CSFM for Class I, Div.1 groups B,C & D (2) 34 NPT with SS4-FSCHCOM SS4 Module HART Factory installed.
    SS4-A2-H
    SS4-A2 Aluminum UVIR, FM, Hydrocarbon Fires, Non Latching Alarm LED, FM, cFM, CSFM for Class I, Div.1 groups B,C & D (2) 34 NPT with SS4-FSCHCOM SS4 Module HART Factory installed.
    SS4-AS
    UVIR AL NPT LCH LED FM HCFN
    SS4-AS
    UVIR AL NPT LCH LED FM HCFN
    SS4-AS2-C-E-H
    SS4-AS2-C-E Aluminum UVIR, ATEX, optimised for Non-Hydrocarbons and Silane, Ethanol, Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM, CSFM for Class I, D installed.
    SS4-AS2-C-E-H
    SS4-AS2-C-E Aluminum UVIR, ATEX, optimised for Non-Hydrocarbons and Silane, Ethanol, Methanol, Hydrogen & Natural Gas Fires, Non Latching Alarm LED, FM, cFM, CSFM for Class I, D installed.